GP5000-G-HV-AS
Model Numbers: GP5000-G-HV-AS, GP5000-G-HV-AS-D1, GP5000-G4-HV-AS-D1
Automatic Insulation Resistance Tester that monitors and protects critical-duty generators
GenGuard applies a current limited, fixed DC voltage to the generator’s windings during idle periods. On four wire neutral grounded systems the ground interrupter automatically opens the neutral ground while the GenGuard is testing the windings. The ground interrupter safety circuit will not allow the generator to operate unless the neutral ground is closed. A solid state comparator circuit monitors measured leakage current to ground. Two adjustable set points, factory preset to customer specifications, can be programmed to signal a pre-alarm, alarm and lockout the equipment from operating if the low set point is exceeded. The manual reset feature enables a return to operational status only after the alarm condition has been corrected. GenGuard will not impair normal operation of the equipment being monitored.
Specifications
Input Voltage: 120 VAC, (optional 240 VAC), 50/60 Hz
Input Current: .15 A max. @ 120 VAC
Test Voltage: 2500/5000 VDC @ 350 μA max.
Maximum Line Voltage: HV model – 15 KV
Control Sensing: N/O Contact or 120 VAC, 50/60 Hz
Alarm Time Delay: 0 – 2 Minutes
Alarm/Lockout Contacts: 1 Form C, 5A @ 240 VAC or 28 VDC
Pre-Alarm Contact: 1 Form C, 5A @ 240 VAC or 28 VDC
LED Display:
Power On: Green
Test On: Yellow
Pre-Alarm: Yellow Flashing
Alarm: Red Flashing
Meter Output: 1% Analog Signal
Accuracy: 1% Overall
Ambient Temperature: -20° F to 140° F
Size: 12″ H x 4″ W x 8.50″ D
Weight: 7.5 lbs.
Assembly: Meets UL 508/61010 specifications
Documents
Features
- Single Generator Model
- Auto/Manual test operation
- Adjustable alarm and pre-alarm set points
- Latching alarm contacts with manual reset
- Pre-alarm contacts with auto reset
- Fused input and H.V. test lead
- 15 ft. two-way current-limited H.V. test lead w/plug
- 2500 VDC/5000 VDC test voltage
- Remote Calibration and system test switch
- Long-life, flashing remote LED/switch assembly w/15 ft. cable
- 1% Panel meter with 4” color coded dial
- Ground Interrupter safety interface
- 10 Year Warranty
Optional Features
- Panel Meter