GP500-M-AS
Model Numbers: GP500-M-AS, GP500-M-AS-D, GP500-M-AS-D1,
MotorGuard applies a current limited, fixed DC voltage to the motor windings during idle periods. A solid state comparator circuit monitors measured leakage current to the ground. Two adjustable set points, factory preset to customer specifications, can be programmed to signal a pre-alarm, alarm and lockout the equipment from operating if the low set point is exceeded. The manual reset feature enables a return to operational status only after the alarm condition has been corrected. MotorGuard will not impair normal operation of the equipment being monitored.
Specifications
Input Voltage: 120 VAC, (optional 240 VAC), 50/60 Hz
Input Current: .05 A max. @ 120 VAC
Test Voltage: 500 VDC @ 200 μA max.
Maximum Line Voltage: 600 V RMS
Control Sensing: N/C Contact
Alarm Time Delay: 0 – 10 Seconds
Alarm Contacts: 1 Form C, 2.5A @ 240 VAC or 28 VDC
Lockout Contact: 1 N/C, 5A @ 240 VAC or 28 VDC
LED Display: Test On: Green; Alarm: Red Flashing
Accuracy: 2% Overall
Ambient Temperature: -20° F to 140° F
Size: 2.87″ H x 2.95″ W x 4.50″ D
Weight: 1 lbs.
Assembly: Meets UL 508/61010 specifications
Documents
Features
- Single Motor Go/No Go Model
- Auto/Manual test operation
- Adjustable alarm set point
- Adjustable pre-alarm set point
- Latching alarm contacts with manual reset
- Fused input and test output
- 500 VDC test voltage
- Long-life, remote LED/switch assembly
- Compact, lightweight enclosure
- DIN Rail mounting bracket
- 10 Year Warranty